Worked Example · External Wall

Cavity Wall U-Value Worked Example

A typical insulated masonry cavity wall for a new-build dwelling in England, checked against the Approved Document L (2021) limit of 0.18 W/m²K for external walls.

Build-up layers

#LayerThickness (mm)λ (W/m·K)R (m²K/W)
—External surface resistance (Rse)——0.040
1Outer leaf brickwork1020.7700.132
2Clear cavity (air space)(air space)50—0.160
3PIR insulation board1200.0225.455
4Inner leaf aerated block1000.1900.526
5Plaster130.5000.026
—Internal surface resistance (Rsi)——0.130

Calculated U-value

0.155 W/m²K

Total resistance R = 6.469 m²K/W

ADL 2021 limit

0.18 W/m²K

England — Approved Document L (2021), new dwellings

PASS

The calculated U-value of 0.155 W/m²K is at or below the 0.18 W/m²K limit — compliant with ADL 2021.