Worked Example · Ground Floor (floating)

Ground Floor (Floating) U-Value Worked Example

An insulated ground-bearing concrete slab, assessed with the ISO 13370 simplified method and checked against the Approved Document L (2021) limit of 0.11 W/m²K for ground floors.

Build-up layers

#LayerThickness (mm)λ (W/m·K)R (m²K/W)
—External surface resistance (Rse)——1.459
1Screed650.4100.159
2PIR insulation2000.0229.091
3Concrete slab1502.0000.075
—Internal surface resistance (Rsi)——0.170

Perimeter/area ratio: P/A = 40/100 = 0.40 m⁻¹

Calculated U-value

0.091 W/m²K

Total resistance R = 10.953 m²K/W

ADL 2021 limit

0.11 W/m²K

England — Approved Document L (2021), new dwellings

PASS

The calculated U-value of 0.091 W/m²K is at or below the 0.11 W/m²K limit — compliant with ADL 2021.