Worked Example · Flat Roof (warm)

Flat Roof (Warm) U-Value Worked Example

A warm flat roof build-up with insulation above the structural deck, checked against the Approved Document L (2021) limit of 0.11 W/m²K for flat roofs.

Build-up layers

#LayerThickness (mm)λ (W/m·K)R (m²K/W)
—External surface resistance (Rse)——0.040
1Waterproofing membrane30.2000.015
2PIR insulation2000.0229.091
3Plywood deck180.1300.138
4Plasterboard ceiling12.50.2500.050
—Internal surface resistance (Rsi)——0.100

Calculated U-value

0.106 W/m²K

Total resistance R = 9.434 m²K/W

ADL 2021 limit

0.11 W/m²K

England — Approved Document L (2021), new dwellings

PASS

The calculated U-value of 0.106 W/m²K is at or below the 0.11 W/m²K limit — compliant with ADL 2021.